• High frequency on-line double conversion technology

  • DSP (Digital signal processors) control technology

  • Active power factor correction (APFC), input power factor up to 0.99

  • Output power factor 0.9/1.0

  • Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)

  • Auto sensing frequency

  • 50 / 60 Hz frequency conversion

  • Cold start

  • Rear ventilation design and variable speed fan

  • Effective software and hardware protection

  • Quick and stable charging, 90% capacity restored in 3h (standard model UPS)

  • Linear derating in low voltage input reducing battery discharging times

  • Settable delayed start when power is restored

  • Advanced battery management (ABM)

  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode

  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function

MODEL ES901 ES902 ES903
Capacity 1kVA / 1kW 2kVA / 2kW 3kVA / 3kW
INPUT
Rated voltage 208 / 220 / 230 / 240Vac
Voltage range 110 ~ 176Vac (linear derating 50%-100%); 176 ~ 280Vac (no derating); 280 ~ 300Vac (derating 50%)
Frequency 40 ~ 70Hz (auto-sensing)
Power factor ≥0.99
Bypass voltage range - 25% ~ +15% (settable)
Total harmonic distortion (THDi) ≤ 6%
OUTPUT
Voltage 208 / 220 / 230 / 240Vac (settable via LCD)
Voltage regulation ±1%
Frequency 45 ~ 55Hz or 55 ~ 65Hz (sync range); 50/60Hz ± 0.1Hz (battery mode)
Waveform Sinusoidal
Power factor 0.9/1.0
Total harmonic distortion (THDv) ≤2% (linear load), ≤5% (non-linear load)
Crest factor 3:1
Overload 105% ~ 125% for 1min, 125% ~ 150% for 30s, >150% for 300ms
BATTERIES
DC voltage 24V(S), 24V(H), 36V(S), 36V(H), 48V(S), 48V(H), 72V(S), 72V(H), 72V(S), 72V(H), 96V(S), 96V(H)
Inbuilt battery 2×9Ah, 3×7Ah, 4×9Ah, 6×7Ah, 6×9Ah, 8×7Ah
Charging current (max.) Standard model: 1A, long time model: 6A
Recharge time Standard model: 90% capacity restored in 3 hours; Long time model: depend on battery capacity
SYSTEM
Efficiency ≥90% (Mains)
≥85% (Batt)
≥95% (ECO)
≥91% (Mains)
≥86% (Batt)
≥96% (ECO)
≥92% (Mains)
≥87% (Batt)
≥97% (ECO)
Transfer time Mains mode to battery mode: 0 ms; Inverter mode to bypass mode: 4 ms (typical)
Protections Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communications RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
Display LCD + LED
Standards EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4 series
OTHERS
Operating temperature 0℃ ~ 40℃
Storage temperature -25°C ~ 55°C (without batteries)
Relative humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m ≤ 50dB
Dimensions (W×D×H) (mm) 144×312×216, 144×336×214, 144×371×216, 144×336×216, 144×417×216 191×418×335, 191×419×335, 191×418×335, 191×419×335, 191×418×335 191×419×335, 191×418×335, 191×418×335, 191×335, 191×418×335
Packaged dimensions (W×D×H) (mm) 230×402×315, 232×417×318, 230×460×315, 232×417×318, 230×506×315 277×500×435
Net weight (kg) 11 / 6 / 12.8 / 6 / 16.4 10.5 / 23.1 / 10.5 / 24.3 / 11 29.4 / 11
Gross weight (kg) 11.3 / 6.9 / 14 / 7 / 17.8 11.6 / 24.7 / 12 / 25.9 / 12.5 31.1 / 12.5
Call Now Button